Abstract
A study was conducted on the extra high voltage (EHV) French power system in order to explore the extended equal-area criterion and test its suitability as a fast transient stability indicator. The assumptions underlying the method are reexamined, causes liable to invalidate them are identified, and indices are devised to automatically circumvent them. The selection of candidate critical machines is also reconsidered, and an augmented criterion is proposed. The various improvements were developed and tested on about 1000 stability scenarios, covering the entire 400 kV system. The severity of the scenarios, resulting from the combination of weakened pre and post-fault configurations, subjected the method to particularly stringent conditions. The simulation results are summarized. >
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.