Abstract

Implementation of vapor-liquid separation during condensation enhances heat transfer and reduces pressure drop. Multi-pass-orifice header as a liquid-separation unit has been widely used in liquid-separation condenser (LSC). Its vapor-liquid separation characteristics, which are vital to LSC, are however barely reported. This paper employs CFD to reveal the flow features thereof. Simulation is initiated by applying an existing header in LSC (Case 0). Results show that the strong fluid-impact leads to considerable vapor leakage in orifices. By avoiding this, the orthogonal test (Case 1 to Case 9) is carried out to screen the orifice layout. It is observed the separation efficiency (η) is mostly affected by the orifice diameter, followed by its position and number. A better η is obtained when the orifices have diameter of 1.5 mm and are distributed on two thirds of header diameter (2D/3) as well as has the number of three (Case 5). Thereafter, two extra combinations of different orifice diameters (Case 10 and Case 11) are further studied. The obtained best η of 51.9% occurs at Case 11, in which it has a larger pressure difference (∆P) and more even flow distributions. Finally, some comments are addressed to pinpoint the significance of this study.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.