Abstract
Overhead line conductors can generate audible noise across a wide frequency spectrum as a result of elevated electric fields at the conductor surface. Such fields are enhanced by the presence of surface defects, insects, water drops and pollution. Within this paper, the impact of a superhydrophobic coating on the audible noise produced by an overhead line conductor is examined. Noise levels from a conductor coated with a superhydrophobic coating were compared to those from a bare conductor in a semi-anechoic chamber. The conductors were energised at voltages to provide surface electric fields ranging from 6 kV/cm to 21 kV/cm (rms). With a continuous water spray system depositing droplets on the conductor surface, the frequency domain sound pressure level, overall sound pressure levels and corona discharge magnitude were measured. It is demonstrated that the use of a superhydrophobic coating reduced audible noise levels and corona discharge magnitude, especially at electric fields above 14 kV/cm. The image analysis suggests that the water drop size distribution and the position of surface droplets on the conductor circumference play an important role in the magnitude of audible noise.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.