Abstract

With the vigorous spread of renewable energy, much attention has been paid to natural ventilation. The natural ventilator is usually classified into a passive type and an active type. In this study, the Venturi-type ventilator, which is one of the passive type and basically operated by the Bernoulli’s principle, was experimentally investigated to evaluate the ventilation characteristics according to the outdoor wind velocities and the opening area of a wall. It was confirmed from the experimental results that the ventilation rate of the Venturi-type ventilator was linearly increased and that the ventilation rate was affected by an intake opening area. The wider the intake opening size gets, the more the ventilation rate increases. Furthermore, the new coefficient of β, which reflects the pressure loss from the intake opening to the mixing zone of the Venturi-type ventilator was introduced and experimentally evaluated. The value of β, which was evaluated as about 0.08, provides the simple calculation means to estimate the ventilation rate through the Venturi-type ventilator only if the geometric dimensions are known.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.