Abstract

In this paper, an industrial-scale experiment with ten testing heat exchangers is conducted to study the influences of structures and working conditions on the tube-side heat transfer and flow characteristics of spiral-wound heat exchangers. The experimental results show that, with the increase of the winding angle, the tube-side heat transfer coefficients increase because of the enhanced secondary flow and slightly larger velocity. The compactness of the whole heat exchanger changes with the variations of the layer and tube pitch. When layer pitch and tube pitch decrease, the flow channel in the shell side is narrowed down, which makes the overall heat transfer temperature difference decrease and finally results in deterioration of the heat transfer in the tube side. For the friction factors, they decrease when the winding angle decreases due to the different turbulence status and velocities in the tube. As a parameter of working condition, the tube-side inlet temperature has a slightly negative effect on the heat transfer. Based on the experimental data, the correlations of Nusselt number and friction factor are developed. Comparing the experimental data and the correlations, the average errors of the Nusselt number and friction factor are 8.04% and 6.28%, respectively.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.