Abstract

A calculation method about the radiant cooling load of floor which is based on radiant time series (RTS) method is presented: With the use of radiant time factors, radiant cooling load can be easily calculated from the radiant heat gain. Based on experimental data of total heat gain and total cooling loads collected within 24-hours, radiant heat gain of floor can be calculated through convection and radiation separating method, using PRF/RTF Generator software to calculate the radiant time factor of floor; the radiant cooling load of floor is calculated and compared with the measured values. The results for the 5 experimental conditions show that the radiant cooling load of floor peak error is less than 2.3% comparing with the value which is calculated by radiant time series method, and average error is not more than 3.2%. Its mean absolute error is 1.2% and 1.7% respectively. The experimental study indicated that convection and radiation separating method on wall could calculate the radiant cooling load of floor.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.