Abstract

The audible noise produced by corona discharge from transmission line conductors comprises two major components, namely hum noise and random noise. Hum noise has a frequency that is twice the power line frequency and is generated primarily in rain, fog, and highly humid environments. It is one of the major factors affecting the design of conductor transmission lines for voltages above 500 kV, and it is very important to predict the level of hum noise near transmission lines. In this paper, using a comparison between measured values in the UHV Akagi test line and that using corona cage, an experimental prediction method of hum noise in rain condition is proposed. © 1998 Scripta Technica, Electr Eng Jpn, 125(1): 27–36, 1998

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.