Abstract

Energy saving significantly and positively affects energy conservation and releases less carbon dioxide. This study aims to investigate the energy-saving characteristics of a novel parallel-flow heat pipe heat exchanger (PFHP-HE) in air conditioning. It merged the characteristics of high axial heat transfer performance of heat pipe with high external heat transfer performance of parallel-flow heat exchanger (PF-HE). The test rig for the PFHP-HE was built on the basis of the heat transfer wind tunnel in this work. The heat transfer performance of parallel-flow heat pipe heat exchanger charged with R600A as the working fluid was experimentally studied. The filling rate of the heat pipe was 26%, and its thermal behavior was analyzed. The evaporation section of the PFHP-HE was heated by heating belt. The experiment was conducted with heating power of 500W. The experiments were performed with cooling air flow rates ranging from 63.36 m3/h to 118.08 m3/h. The results indicate that when the airflow rate was 118.08m3/h, the minimum thermal resistance of the PFHP-HE was 0.06 K/W, and the heat transfer efficiency was up to 98% in the experiments. As the pulsation phenomenon was caused by its small diameter, the temperature distribution in condenser had stratified phenomenon in PFHP-HE. The PFHP-HE has excellent heat transfer performance and working stability. The PFHP-HE is a promising heat exchanger for energy-saving in air conditioning. Its superior heat transfer performance and working stability make it an attractive alternative to conventional heat pipe heat exchangers.