Abstract

Hybrid ground source heat pump systems (HGSHPS) with assisted cooling towers is one of the most efficient cooling and heating technologies for buildings with cooling-dominated loads. For the system, the coupled heat release mode between the ground heat exchanger (GHE) and cooling tower is vital for underground soil temperature recovery characteristics and system operation performance. In order to obtain the heat release operation characteristics with different coupled modes of the GHE and cooling tower, a set of multi-functional heat release experimental systems of soil coupled GHE with assisted cooling tower was constructed. The experimental investigations on the system heat release operation characteristics operated in the separate GHE heat release mode, combination heat release mode and day and night alternate heat release mode were undertaken based on the experimental system. The results show that for the separate GHE heat release mode, the heat release rate of GHE rises rapidly during the first two hours of operation, then, gradually tends to be steady, and the soil excess temperatures at various depths gradually rise with time. For the combination heat release mode with continuous operation of cooling tower, in view of reducing soil heat accumulation and accelerating soil temperature recovery, it is more conducive to the heat release by opening the cooling tower on sunny days. For the combination heat release mode with intermittent operation of cooling tower, when the total time ratio of cooling tower running to stop is constant, the intermittent time is longer, the better the effect of soil temperature recovery. Additionally, the soil temperature recovery rate can be improved greatly by the release heat operation of cooling tower during night, and the longer the cooling tower runs, the closer the soil temperature is to the initial temperature.

Highlights

  • Energy shortage and environmental pollution have given rise to the utilization of clean and renewable energy sources

  • The advantages of ground source heat pump (GSHP) could be weakened in cooling-dominated districts where the building annual total cooling load is greater than total heating load and more thermal energy is released into the ground than extracted from it

  • The results show that the artificial neural network (ANN) model could ensure that the absolute temperature error is within 0.2 ◦ C

Read more

Summary

Experimental Study on the Heat Release Operational

State Key Laboratory for Geo Mechanics and Deep Underground Engineering, China University of Mining. Key Laboratory of Thermo-Fluid Science and Engineering (Xi’an Jiaotong University), Ministry of Education, Xi’an 710049, China. Key Laboratory of Efficient & Clean Energy Utilization, the Education Department of Hunan Province, Changsha 410114, China. Received: 3 December 2017; Accepted: 26 December 2017; Published: 1 January 2018

Introduction
Components of the System
Measurement System
Experimental Performance Analysis
Combination Heat Release Mode
Day and Night Alternate Heat Release Mode
Experimental Data Processing
Error Analysis
Separate GHE Heat Release Mode
Variation curve of heat release separateGHE
Mode 2
Conclusions
Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.