Abstract

In this paper, the frosting experiment was carried out by the wind tunnel experimental device in the single experimental section of the closed-mouth return flow. Through the experimental study on the influence of heat exchange temperature difference on the growth characteristics of the frosting layer in the finned evaporator under the experimental conditions of different initial head wind speeds, the following conclusions were drawn: At 2m/s, the frost thickness of finned tube evaporator increases gradually with the frosting time at different heat exchange temperature differences. At 3, 4, 5m/s initial face wind speed, the frost thickness of finned tube evaporator grows in a three-stage pattern at different heat exchange temperature differences. The cooling capacity of the evaporator at different face wind speeds and different heat transfer temperature differences increases first and then decreases with the frosting time.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.