Abstract

An experimental test series, comprising 10 experiments with varying pool sizes, lining materials and amounts of liquid burning, was conducted under free burn and room burn conditions. The thermal feedback from the enclosure (ISO 9705 Room Corner Test facility) enhanced the burning rate of the pools and resulted in a thermal runaway in some of the runs. The onset of the thermal runaway, which can be associated with flashover, varied with all the input parameters. The lining with the lowest thermal inertia lead to the fastest increase in the heat release rate (HRR) in the enclosure and caused flashover in the shortest time. Given the profound difference between the enclosure tests and the free burn tests and also between enclosure tests with different linings, it is recommended to show great caution if free burn tests are to be used in design fire scenarios.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.