Abstract

Some flashover incidents of high-voltage transmission lines are reported to be induced by fire. Though the mechanism of fire induced flashover is not well understood, it is deemed that fire could reduce the insulation strength of air. This paper has compared the breakdown characteristics of gaps in normal air conditions and those in fire. The results show that the breakdown voltage or electric field strength of gaps in fire decreases greatly. The value of breakdown electric field strength in alcohol flame is about 1.454 KV/cm, which is only about 28.8% of that in air. The value of breakdown electric field strength in wood crib fire is about 0.300KV/cm, corresponding to 19.9% of that in air. This study demonstrates that flame and soot particle of fire are responsible for fire induce flashover of high-voltage transmission lines.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.