Abstract
This study tested gas sensors used to measure indoor air quality to explore the feasibility of using them as detection sensors in case of fire. A B-class fire environment was implemented in the compartment (ISO 9705 standard fire room), and four types of high- and low- accuracy and priced gas sensors (Carbon monoxide, carbon dioxide, methane, t-VOC) used for indoor air quality measurement were installed. From ignition of the fuel to alarming of the heat detector, the responses from the sensors were analyzed. The results revealed the following: 1) Among the four types of sensors, CO and t-VOC sensors were effective as fire detection sensors in terms of their concentration increase and response time. 2) Low-accuracy CO2 and CH4 sensors were not effective in fire detection as they responded late relatively to CO and t-VOC sensors. 3) It was confirmed that low-accuracy gas sensors are feasible for use for fire detection in that they showed valid increase in concentration before the heat detector alarms. However, as only liquid combustible (Heptane) was applied as a fire source, analysis in an environment where different types of combustibles are used will be necessary in the future.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.