Abstract

Experiments were performed by using water and paraffin slurry to investigate thermal characteristics from a test multichip module. The parameters were the mass fraction of paraffin slurry (0, 2.5, 5, 7.5%), heat flux (10, 20, 30, 40 W/cm2) and channel Reynolds numbers. The size of paraffin slurry particles was within 10–40 μm. The local heat transfer coefficients for the paraffin slurry were larger than those for water. Thermally fully developed conditions were observed after the third or fourth row. The paraffin slurry with a mass fraction of 5% showed the most efficient cooling performance when the heat transfer and the pressure drop in the test section were considered simultaneously. A new correlation for the water and the paraffin slurry with a mass fraction of 5% was obtained for a channel Reynolds number over 5300.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.