Abstract

In view of the low refrigeration efficiency of the refrigeration system of the pure electric logistics car under the high temperature environment, an experimental platform of the refrigeration system based on medium pressure air supply of the pure electric refrigerator car was built with R404A as the refrigerant, the experiment results show that the system refrigerating capacity, COP and EER decrease with the increase of external environment temperature under the same internal environment temperature, the compressor power and exhaust temperature increase with the increase of the external environment temperature. When the external environment temperature is 43 °C, the medium pressure air supply technology is obviously better than the non-air supply technology, the refrigerating capacity increased by 4.1–12.73 %, the compressor power and EER changed little, the COP increased by 1.3–6.38 %, and the exhaust temperature reduced by 3.4 °C-7.11 °C, especially at -3 °C, the system refrigerating capacity decreases by 30.1 %, the compressor power increases by 35.6 %, the COP and EER distribution decreases by 51.24 % and 42.68 %.