Abstract

In the 1999 AISC-LRFD, the in-filled concrete strength ( f c ′ ) of concrete-filled tube (CFT) columns is limited to a maximum value of 55 MPa (N/mm 2). That limiting value is raised to 70 MPa in the 2005 AISC-LRFD. This study aims to assess if the LRFD CFT column formulas are applicable to intermediate to long rectangular columns with higher concrete strengths. Twenty four specimens with f c ′ varying between 29 and 84 MPa were tested. Various formulas and relevant provisions for CFT columns as specified in the major design codes including AISC-LRFD, EC 4, AS-5100, and CSA S16-01 were examined and compared. The design CFT strength ( P u ) predicted by the AISC-LRFD formulas and the test results ( P test ) were found to be in good agreement. The higher f c ′ limiting value of 70 MPa proposed in the 2005 AISC-LRFD appears acceptable. The test results reveal that the 1999 AISC-LRFD design strengths are conservative and tend to penalize these CFT columns with higher concrete strength.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.