Abstract

Boiling heat transfer of R-600a in a 2.6 mm ID tube was investigated. Experimental conditions comprised heat fluxes of 44–95 kW m−2, mass velocities of 240 and 440 kg m−2 s−1 and saturation temperature of 22 °C. The effect of heat flux on the heat transfer coefficient was significant at low vapor qualities for the lower mass velocity. Frictional pressure drops increased with vapor quality and mass velocity. In comparison with R-134a, R-600a provides higher heat transfer coefficients and pressure drops. For the prediction of the heat transfer coefficients, the correlation of Kandlikar and Balasubramanian (2004) best fitted the experimental results, through the adjustment of a model coefficient. For frictional pressure drops, deviations from results obtained by usual correlations were quite large. The present results extend the ranges of heat flux and mass velocity beyond those available in the literature for R-600a, and thus represent a substantial contribution to the theme.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.