Abstract

Pressure measurement with insulation tubes is successfully performed at the nozzle throat, in the upper flow path and in the thermal room for the two types of tandem-puffer (self-blast chamber) adopting different gas blast angle of nozzle. The pressure rise mechanism with auto-expansion effect of arc is discussed. The pressure rise in the upper flow path and the thermal chamber is driven by propagation of pressure wave from the arc to the thermal chamber. And several types of oscillation caused by rarefaction wave after the pressure wave and multi-reflection of the pressure wave are superposed on the pressure profile. Finally, an influence of the gas blast angle of the nozzle on cooling of stagnation point (thermal interruption capability) is explained based on the results of these measurement and 2-dimensional thermo-fluid analysis. A little larger gas blast angle of the nozzle leads to stronger gas flow to the stagnation point caused by a little larger resistance to the pressure wave and the gas flow.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.