Abstract
The efficacy of a four-bed adsorption chiller has been studied experimentally with respect to a simple but yet effective passive heat and mass recovery schemes. It substantially improves the adsorption chiller COP by as much as 30% over a broad range of cycle time with a wide heat source, coolant and chilled water temperatures. Two schemes have been considered here: Firstly, only the mass recovery is achieved by pressure equalization between the concomitantly cooled adsorber and heated desorber, exploiting the intrinsic vapor-uptake potential by pressure swing that remains in the adsorbent at the end of a half-cycle. Secondly, when both the heat and mass recovery schemes are employed at a rating point of maximum cooling capacity, the chiller COP could increase further to as much as 48%. These improvements are performed without additional hardware changes to the adsorption chiller.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.