Abstract
The fire characteristics under natural ventilation in the cable compartment of the utility tunnel are studied. A series of small-scale fire experimental tests are conducted to obtain the maximum temperature below the ceiling of different ignition vertical heights and cable types. In this paper, the ceiling temperature decay and heat release rate (HRR) are studied in the cable compartment of utility tunnel. Through experimental tests, the fire characteristics of placing the fire source on the near wall side 3.0 m away from the shaft of the utility tunnel cable compartment are studied. The results showed that under the action of natural ventilation, with the decrease of fuel quantity, the mass loss of cable decreases, and the maximum temperature below the ceiling of the cable compartment in the utility tunnel decreases. ZRYJV cables burn more sufficient combustion than RVVR cables. A new empirical association for total HRR is proposed. Those experimental test results are used as validation data for the newly proposed empirical correlation of total HRR. This paper hopes to provide some basic fire safety references for the utility tunnel planning of the urban underground cable compartment.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.