Abstract

ABSTRACTDehumidifier and regenerator are the most important components in a liquid desiccant cooling system. Present paper is focused on study the effect of inlet process parameters on the effectiveness of dehumidifier and regenerator of liquid desiccant cooling system. Experimental study is performed with varying inlet process parameters; mass flow rate of air, desiccant solution flow rate, inlet air temperature, inlet solution temperature, inlet specific humidity and concentration of desiccant solution. Celdek structured pads as packing material and calcium chloride as liquid desiccant is investigated first time using counter flow of the desiccant solution and air. It is concluded from the results that the effectiveness of dehumidifier increases with solution flow rate, inlet specific humidity while decreases with increasing mass flow rate of air, inlet temperature of air and desiccant, temperature and concentration of desiccant solution. The effectiveness of regenerator increases with increasing solution flow rate and inlet desiccant concentration and it decreases with increasing inlet air temperature, air flow rate and inlet solution temperature. Present paper adds to effect of inlet specific humidity, inlet temperature of the air and solution on the effectiveness of desiccant cooling system on the past research.