Abstract

The dew point corrosion characteristics of the heating surface in a 65 t/h biomass-fired circulating fluidized bed (CFB) boiler were experimentally studied. The cross-sectional morphology and composition of the ash deposition were analyzed by scanning electron microscope (SEM), X-ray diffraction (XRD) and X-ray fluorescence spectrum (XRF), respectively. The results showed that the test tube surface was covered by ash deposit layer, coupling layer and corrosion layer. The ash deposit layer and the coupling layer were prone to spall off together. The coupling layer consists of partial ash and corrosion products. The corrosion layer was mainly composed of chlorides (FeCl3, FeCl2, and FeOCl) and oxides (FeOOH, Fe2O3). With the increase of the tube wall temperature, the corrosion depth decreased dramatically and the dew point corrosion was alleviated efficiently. The metal matrix simultaneously suffered from chlorine corrosion and oxygen corrosion. As the tube wall temperature was above water dew point, the main corrosion mode was oxygen corrosion. As the tube wall temperature was below water dew point, the main corrosion mode was chlorine corrosion.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.