Abstract

The purpose of this study is to evaluate the cooling and heating performance as well as the compressor operating conditions of CO2/R32 blends in a water-to-water heat pump system. Experiments were conducted to reveal the effects of the refrigerant compositions, heat source temperatures, and internal heat exchanger (IHX) on the performance of the system. The results show that 23.3% and 65.2% maximum improvement in heating coefficient of performance (COPh) and cooling coefficient of performance (COPc) of the system were obtained when the mass fraction of CO2 was 0.6, respectively. Meanwhile, heating capacity, cooling capacity, and the compressor discharge pressure of CO2/R32 blends were decreased significantly. The thermal matching between the heat source and CO2/R32 blends significantly affected the overall performance of the system. In addition, IHX is recommended in the water-to-water heat pump to improve the system performance.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.