Abstract
This paper studies water mist fire suppression under different longitudinal ventilation velocities in tunnels by small-scale experiments. After a scaling study, two mist nozzles are used for suppressing crib fires under 5 ventilation speeds. The result comes out that fire suppression process can be divided into three stages including flame unitary restraining stage, surface flame extinguishing stage and inside flame suppression stage. Several factors influencing efficiency are investigated. When the interval between mist nozzle and fire source enlarges, the relationship curve between fire suppression time and ventilation velocity shows a ‘V’ figure. The best ventilation speed exists. Following the rules summarized, a coupling system of water mist and ventilation may increase fire suppression efficiency remarkably.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.