Abstract
AbstractIn this study, copper foam was used as a porous medium in place of traditional aluminum fins. A comparison between the two heat exchangers—one with fins and the other with copper foam—was conducted under various conditions. The air inlet velocity ranged from 0.9 to 9.3 m/s, and the water inlet temperature ranged from 10°C to 18°C. Different water flow rates were tested. A comparison was made between the performance of copper foam and aluminum fins by calculating several parameters, including thermal resistance, heat exchanger effectiveness, Colburn factor, Nusselt number, friction factor, and area goodness factor (AG). The experimental results showed that at low air velocities, the heat transfer coefficient for both types of heat exchangers was almost equal. However, at high air velocities, the copper foam exhibited a higher heat transfer coefficient. The Colburn factor was higher for the heat exchanger with copper foam than in the conventional fins, where it was equal to 0.1959 for the copper foam and 0.1186 for the fins. On the other hand, the AG was higher in the case of fins than in the heat exchanger with copper foam.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.