Abstract

Water suppression experiments of EPS and XPS are conducted in Standard Combustion Chamber in USTC in Hefei. The 20 cm * 20 cm PSs were held against a 600 mm*600 mm vertical gypsum board fixed by a steel frame structures to simulate a building facade. A series of results have been obtained. When the water spray is not applied, the EPS is easier to melt, drip and pyrolyze than XPS under the same fire load, but causes less amount of CO than the amount of XPS without any water application. When the water is applied, neither EPS nor XPS has a trend to drip. The amount of CO caused by EPS or XPS under water spray is much less than that of non-spray. Also the extinguishment time falls fast once the PS materials are applied with water. In addition, these experimental results demonstrate the feasibility of the designed rig in studying the fire suppression on vertical PS materials using water spray.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.