Abstract
Grounding system is the most crucial area in power system network. Poor grounding system can be dangerous to the users and wire of the electrical distribution system in the event of electrical fault. To prevent this accident, it is very important to have a good grounding system to protect the system as well as to the user. Therefore, this paper measures the soil resistivity with various planted electrode designs using Wenner Four Point method with the help of equipment earth testers. The experimental works was conducted in clay soil type using copper and iron rod materials. The experimental results show that the new rod design with branches can be considered not suitable to replace the standard rod since the measured soil resistivity was much higher. It is also proven that the copper rod exhibits better value of soil resistivity which can be used for the grounding system.
Published Version (Free)
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.