Abstract
ABSTRACTTo enhance heat transfer and reduce fouling of the finned-tube surface in economizers of coal-fired power plants, heat transfer and pressure drop characteristics for H-type finned oval tube with longitudinal vortex generators (LVG) and dimples, both in-line and staggered arrangements, are studied experimentally under flue dust condition. In addition, the ash samples and heat exchanger surfaces after the test are analyzed to help understanding the ash fouling and tube wear mechanisms. Compared to the original H-type finned oval tube, the Nusselt number of H-type finned oval tube bank with longitudinal vortex generators and dimples is improved by 34.5–41.7% (in-line arrangement) and 28.1–31.7% (staggered arrangement) within the studied Reynolds numbers, while the Euler number is increased by 21.9–28.3% (in-line arrangement) and 19% (staggered arrangement) in the clean finned-tube surface state. In the stable fouling state, the Nusselt number is improved by 37.7–42.3% (in-line arrangement) and 27.8–45.1% (staggered arrangement), while the Euler number is increased by 22.9–25.2% (in-line arrangement) and 33.3–42% (staggered arrangement). The results show that the novel fin structures can both inhibit fouling and enhance heat transfer effectively.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.