Abstract

The condensation heat transfer coefficient and the pressure drop were investigated experimentally and numerically in a microtube condenser using R134a. The microtube condenser comprises of trapezoidal oblique finned microchannel at the top and rectangular fins at the bottom of the tube. Water and air are used as cooling fluids on both sides of the microtube condenser. The experimental setup is validated initially with the existing work of Shah. The condensations effect included the vapour quality and mass flux ranging from 0.25 kg/m2s to 0.9, 99 to 468 kg/m2s, respectively. The results indicate that the condensation heat transfer coefficient and pressure drop enhance with mass flux and vapour quality. The experimental and numerical results are compared with existing experimental work. The microtube condenser enhances the heat transfer coefficient to 22.4% and a pressure drop of 5.6% more than the existing model. The heat transfer coefficient and pressure drop obtained from the numerical study is in superior agreement with the experimental results.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.