Abstract

In this study condensation heat transfer on a cold inclined circular cylinder due to natural convection for various conditions is investigated experimentally. The cylinder is placed in an isolated test room to permit pure natural circulation of ambient air. Ambient temperature and humidity of the test room are controlled by a refrigeration cycle and humidifying. The ambient relative air humidity changed in the range of 30 to 50% and temperature from 25 to 35 °C. The ethylene-glycol/water solution is used as a refrigerant to control and keep the temperature of the test section at a constant value. The cold surface temperature is varied from 2 to 6 °C. The condensation rate and heat flux are found to depend mainly on time, temperature difference between ambient air and cold surface, ambient relative humidity, and tube inclination. Results are plotted for various conditions with respect to time. The experimental results are used to propose a correlation to predict the condensate mass flow rate for free convection heat transfer. © 2012 Wiley Periodicals, Inc. Heat Trans Asian Res; Published online in Wiley Online Library (wileyonlinelibrary.com/journal/htj). DOI 10.1002/htj.21015

Full Text
Published version (Free)

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call