Abstract

Experiments have been performed to study the effects of air on filmwise condensation from steam-air mixtures undergoing forced flow over a 3/4 in. OD horizontal tube. Local condensation rates at the stagnation point are reported for saturation temperatures of 100–150 deg F, bulk to wall temperature differences of 3–30 deg F, bulk air mass fraction 0–7 percent and oncoming vapor velocity 1–6 ft/sec. For pure steam the average value of q/qNu, where qNu is the Nusselt result, was 0.98 ± 0.10, which compares favorably with the value of 1.04 predicted by a theory which accounts for vapor drag. For steam-air mixtures the reduction in heat transfer was found to be in excellent agreement with the theoretical analysis of Denny and South; the average discrepancy in q/qNu was −2.7 percent, while the maximum was 7.1 percent.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.