Abstract

Three cases of cables fire experiments with different ventilation rate in real scale electronic cabinet have been carried out. In each experiment, five cables with 14mm in out diameter and four copper conductors with 1650mm in length were used. the insulation and cover of the cables was combustible .Temperature of the fire cables, CO ,O2as well as temperature in different location in the center of the cabinet in the fire cabinet were measured as a function of time. The key role of the ventilation rate on the temperature in the center of the cabinet and the concentration of CO and O2were clearly shown, but the influence on fire spread of cable fire was not so much significantly.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.