Abstract
The Actual Delivered Density (ADD) for rack-storage fires has been investigated experimentally, using an ADD apparatus equipped with a fire plume simulator. The fire plume simulator was calibrated to simulate the plumes of a 6.1-m (20-ft) high rack-storage fire of the FMRC Class II Commodity. Three standard upright sprinklers (17132-in. C, 112411 F & 112-in. G) were employed for the investigation. Empirical correlations in the form of power law for the water penetration ratio, which is the ratio of the ADD to the water density measured without f i e , have been established for sprinkler-fire arrangements in which the fire was centered under one sprinkler, centered below two sprinklers on the same pipe and centered below four sprinklers. In the case of a single sprinkler operation, the water penetration ratios for a given sprinkler and fire size were found independent of the water discharge rate under the present measurement range, varying from 95 Ilmin to 212 Ilmin (25 gpm to 56 gpm).
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.