Abstract

This paper presents the study of the novel thermoelectric heat pipe heat pumping system. Bent heat pipes with sintered powder wicks were utilized in a configuration which used centrifugal forces, due to rotation, to enhance heat transfer. The revolving heat pipes worked both as a fan and as a heat exchanger; however, extra fan blades were required to improve the fan performance. Fan performance tests were carried out, followed by the thermal performance, within which eight pieces of thermoelectric devices were applied to provide the heat pumping. The results showed that the system could provide airflows of up to 168.7 m3/h with the revolving speed of 600 RPM, and maximum static pressure was up to 37 Pa. The system could supply the heating of up to 257.1 W with the coefficient of performance of up to 1.96. Comparisons were made between the revolving and stationary systems, and the results showed that the former increased the thermal performance by up to 10% in heating and up to 20% in cooling.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.