Abstract

This paper presents an experimental study of the performances of a dual-mode CO2 heat pump system with thermal storage. This CO2 system was tested at a variable frequency compressor, variable expansion valve opening as well as variable frequency cooling/heating water pumps. It is found that the performances of CO2 heat pump with thermal storage can be optimized through optimizing thermal stratification of thermal storage tank coupled with heat pump system performances. High compressor frequency benefits the system performances. Expansion valve opening affects the thermal stratification of thermal storage tanks very slightly. The overall COP reaches a maximum when heating and cooling water flow rates were set as 0.1 m3/h and 0.2 m3/h respectively at compressor frequency of 50Hz and expansion valve opening of 330 pulses.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.