Abstract

This article presents the results of an experimental study performed to develop a computational model of cooling ceiling systems. The model considers the cooling ceiling as a fin. Only the dry regime is considered. From ceiling and room dimensions, material description of the cooling ceiling and measurement of supply water mass flow rate and air and water temperatures, the model calculates the cooling ceiling capacity, ceiling surface average temperature and water exhaust temperature. Fin efficiency, mixed convection close to the cooling ceiling (generated by the ventilation system) and panel perforations influence are studied. The theoretical approach gives to the user an appropriate tool for preliminary calculation, design and diagnosis in commissioning processes in order to determine the main operating conditions of the system in cooling mode. A series of experimental results got on four types of cooling ceilings are used in order to validate the model.