Abstract
Absorber is an important component in vapor absorption refrigeration system and its performance has greater influence in overall efficiency of absorption machines. Falling film heat and mass transfer in an absorber is greatly influenced by fluid properties, geometry of heat exchanger and its operating parameters. This paper presents on the results of experimental studies on the heat and mass transfer characteristics of a coiled tube falling film absorber, using 1,1,1,2-Tetrafluroethane(R-134a) and N-N Dimethyl Acetamide (DMAC) as working fluids. The effects of film Reynolds number, inlet solution temperature and cooling water temperature on absorber heat load, over all heat transfer coefficient and mass of refrigerant absorbed are presented and discussed. Normalized solution and coolant temperature profiles and refrigerant mass absorbed along the height of absorber are also observed from the experimental results. The optimum over all heat transfer coefficient for R-134a–DMAC solution found to be 726 W/m2K for a film Reynolds number of 350. The R-134a vapour absorption rate is maximum in the normalized coil height of 0.6 to 1.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Similar Papers
More From: Heat and Mass Transfer
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.