Abstract

Experimental investigations have been carried out to study heat and mass transfer during desorption of Tetrafluoro ethane (R134a) from R134a and Dimethyl formamide (DMF) solution in a tubular generator. Absorption refrigeration system has been built with brazed plate heat exchangers as condenser, absorber, evaporator and solution heat exchanger and with stainless steel concentric tubes as the generator. Effects of operational parameters viz., solution two phase Reynolds number, driving temperature ratio, driving pressure ratio, solution initial concentration on generator performance are analyzed. Desorption ratio, Sherwood number and Nusselt number increase as the solution Reynolds number, solution initial concentration, driving temperature ratio increase whereas these parameters decrease as the driving pressure ratio increases. Finally a correlation for Nusselt number and Sherwood number are proposed based on the experimental studies.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.