Abstract

The current contribution describes the experiments performed in an outdoor test stand for so called “double-skin-façades” at the Technical University of Munich. The purpose of the investigation was to determine the time and local averaged overall heat transfer coefficients for solar radiation augmented turbulent mixed convection flows in transparent vertical channels. The external plate of the vertical channel is formed with horizontally oriented ventilation gratings in the external glass façade, thus providing openings for the air circulation within the gap. In the course of the research, the distance between the external and the internal glass façade was measured for three gaps of 0.3, 0.6 and 0.9 m wide. Using the pressure compensation method, the effective mass flow rates for a given box-window, which is the smallest functional unit of all known double-skin-façade systems, was measured by means of a ventilation duct installed at the outlet of such a box-window. Finally, the experimental data was reduced in terms of an average Nusselt number as a function of an average Archimedes number for several gap distances.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.