Abstract

A heat-source tower heat pump (HTHP) is a potential heating source for space heating due to frost-free characteristic. The heat and mass transfer between the antifreeze solution and air at low ambient temperatures is a key issue for performance enhancement. In this study, a test bench for evaluating the cross-flow closed-type heat-source tower (CCHT) is fabricated to investigate its performance under variable working conditions. Based on the experimental results, correlations of heat and mass transfer coefficients are developed, which can be used to predict the performance of the CCHT. As a result, the mass transfer coefficient between the solution and the air of the CCHT is 0.015–0.051 kg m−2 s−1, while that of the liquid desiccant dehumidifier is 0.0037–0.015 kg m−2 s−1. However, the latent heat ratio of the CCHT is 6–31%, while that of the liquid desiccant dehumidifier is 42–124%.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.