Abstract

In this study, we study the water source heat pump and digital scroll compressor and experimentally in the multi-connected air-conditioning system. Variable performance is developed when the unit operates in refrigerating and heating mode. The maximum of refrigerating capacity is 36519.95W when inlet water temperature of the condenser is 30°C and dry-bulb temperature of indoor air is 32°C, at the same time the maximum of EER is 4.33 when inlet water temperature of the condenser is 20°C and dry-bulb temperature of indoor air is 27°C. The unit operates in heating mode, the maximum of heating capacity and EER is 33275.73W and 3.86 when inlet water temperature of the condenser is 30°C and dry-bulb temperature of indoor air is 20°C.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.