Abstract

Seismic performance of a UPS through shaking table tests was investigated using the input acceleration time histories with scaling factors of 50%, 100%, and 200%. The first series consists of UPS specimens supported by snip single-corner rectangular pins, and the second series consists of UPS specimens supported by isolator systems. The UPS specimens in the second series significantly reduced the fundamental frequency, peak acceleration, and amplification factors but increased the damping ratio and displacement compared with those of the UPS specimens in the first series. The analytical results obtained from the analytical model agreed well with the experimental results.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.