Abstract

Startup heat load, maximum heat load and optimum fill ratio of Pulsating Heat Pipe (PHP) of 16 turn, 1 mm ID, 2 mm OD and 9.6 m total length are found out experimentally for water and ethanol as working fluids. PHP is operated in vertical bottom heat mode. Evaporator and condenser temperatures are maintained at 100 °C and 28 °C respectively. Temperature fluctuations of adiabatic section at startup and maximum heat loads are reported. Experimental results indicate that, startup heat load is independent of fill ratio, but maximum heat load depends on fill ratio. Optimum fill ratio for maximum heat load depends on working fluid for a given PHP and operating temperatures.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.