Abstract

In this article, an experimental study has been conducted to provide better understanding of the transient characteristics of a dual compensation chamber loop heat pipe (DCCLHP) subjected to the acceleration force. A new acceleration test rig was set up to provide the acceleration up to 11g with three different directions. The heat load on the evaporator ranging from 25 W to 300 W was applied with the acceleration force simultaneously. Experimental results indicated that the DCCLHP could start up at a small heat load of 25 W and the startup behavior was different under acceleration direction conditions because of the vapor-liquid distribution change in the evaporator and compensation chambers (CCs). Under the current operating conditions, the effect of acceleration force was significant to the operating performance at small heat loads whereas was weak at large heat loads. Experimental results also clearly showed that both acceleration magnitude and direction can alter the operating mode. What’s more, it was found that temperature oscillation, reverse flow and evaporation in the evaporator core phenomena occurred under acceleration conditions.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.