The purpose of this study is to investigate the thermal performance of heat recovery system with gravity assisted heat pipe charged R134a and R410A working fluids and also determine the usefulness of heat pipe bundle system in heat recovery applications. For this purpose an experimental test rig was designed and built. Series of experimental tests were carried out by varying the flue gas temperature (75, 100, 125, 150 and 175 °C), flue gas velocity (1, 1.5, 2 and 2.5 m/s) and cooling water flow rates (1, 2, 3 and 4 l/min). Values of the overall effectiveness of the heat pipe heat recovery system are shown to vary with the flue gas velocity, as expected, but the results also allow the prediction of effectiveness variation with the variation of the flue gas temperature. Effectiveness of the heat pipe for both working fluids R134a and R410A has been varied averagely between 35.6% and 57.7% with a good agreement with the published results. Quantitatively, it is found that R134a working fluid is 14% more effective than R410A in heat pipe bundle system.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.