Abstract

To improve the performance of scroll refrigeration compressor, an external cooling structure scroll compressor was designed and researched. A prototype with cooling structure was developed and tested. The thermodynamic model including the leakage, heat transfer, and friction was set up to simulate the working process of scroll compressor with external cooling. Experimental results show that coefficient of performance value of the prototype is improved by 0.31, the cooling capacity increases by 1281 W (12.9 per cent) and the discharge temperature reduces by 44 °C (41 per cent) maximally when the water cooling is used. Increasing the water flowrate improves the volumetric efficiency and enhances the heat transfer between water and scroll compressor. When the rotational speed of compressor goes up, the volumetric efficiency increases remarkably while the quantity of heat transfer rises slowly. The simulated results have good coincidence with the experimental ones.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.