Abstract

During the defrosting process in cold regions, the air source heat pump with vapor injection encounters some problems, e.g. long defrosting time and low defrosting efficiency. To solve these problems, a new defrosting strategy through injecting medium-pressure vapor refrigerant into compressor during defrosting process was proposed based on its special structure. Five groups of experiments having different openings of injection electronic expansion valve were designed and conducted to investigate the effect of this defrosting strategy. Results indicate that an optimal opening of injection electronic expansion valve exists during defrosting process with vapor injection. For the experimental air source heat pump, it is 50%. At the opening of less than 50%, the experimental unit can run safely and defrosting performance improves gradually with the opening increase. When the opening increases to greater than 50%, the defrosting process is unsteady. At the optimal opening of injection electronic expansion valve, the defrosting time and power consumption are respectively decreased by 20.61% and 17.98%, while the defrosting efficiency is improved by 6.22%.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.