Abstract
This paper presents the results of an experimental installation with an internal melt-ice-on-coil tank which has a total capacity of 172 kWh. The aim of this work is to analyse the freezing process in a tank with counter-current spiral-shaped coils immersed in around 1855l water. An experimental campaign has been performed with different inlet temperatures and mass flow rates of the heat transfer fluid. This study analyses (i) the chiller performance, (ii) the ice-formation process and (iii) the energy consumption of the installation. Supply temperatures between −2.5 °C and −5.2 °C have been sufficient to charge the tank without using any nucleating agents. The lowest energy consumption has been achieved for the fastest charging tests.
Talk to us
Join us for a 30 min session where you can share your feedback and ask us any queries you have
Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.