Abstract

Abstract This paper presents a field study for the performance of photovoltaic thermal (PVT) system that use aluminium cooling plate with straight and helical channels during July 2016. Three systems each of 0.37 m2 commercial poly-crystalline PV panels have been installed at the faculty of engineering at Shoubra, Benha University, Cairo, Egypt (30.1°N Latitude). Two of the systems are cooled using straight and helical channels with dimensions of 10 × 10 mm 2 and compared with the uncooled panel. The results showed that an increase in average electrical efficiency of 17.7% to 38.4% with relative to uncooled panels for flow rate range of 0.25 to 1 L/min. The corresponding average thermal efficiency increases from 31.6% to 47.2% for straight channels and 34.6% to 57.9% for helical configuration. While the corresponding average exergy efficiency increases from 11.1% to 12.9% for straight channels and 11.5% to 13.5% for helical arrangement. The associated water pumping power in both configurations does not exceed 3.3% of the converted electrical power while the increase in the obtained electrical power is of 30% with relative uncooled cell power.

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.