Abstract

Tests with new samples are conducted to investigate the aging process of repeated low-level dry band arcing on ADSS cables. Based on the experiments and analysis, the process can be divided into three stages: sparking, short-term dry band arcing and stable dry band arcing. Their characteristics are described respectively. The length of stable dry band arcing is measured. The relationship between the length of dry band arc and leakage current is derived under given applied voltage. The effect of applied voltage and leakage current on the aging cycle is also studied. Experiments show that no damage or failure happens with 1mA leakage current. When applied voltage is above 7kV, dry band arcing causes failures under 2mA leakage current.

Full Text
Paper version not known

Talk to us

Join us for a 30 min session where you can share your feedback and ask us any queries you have

Schedule a call

Disclaimer: All third-party content on this website/platform is and will remain the property of their respective owners and is provided on "as is" basis without any warranties, express or implied. Use of third-party content does not indicate any affiliation, sponsorship with or endorsement by them. Any references to third-party content is to identify the corresponding services and shall be considered fair use under The CopyrightLaw.